> Many of the less expensive CT / AC ammeter setups are nonlinear at the
> bottom of the scale.  You have to have enough current to get at least 10
> - 15% of a full scale reading to make them work accurately.  This is
> because the meter movement inside the analog meter is actually a DC
> movement driven by  a diode bridge, and you have to apply enough voltage
> to the terminals to overcome a couple of diode forward voltages to get
> the pointer to budge.  Once the diode bridge in the input circuit is
> fully conducting, the readings will be valid.
    and some AC meters use AC movements.  Depending on
    the type, these can give nonlinear indications, the scale will
    be nonlinear...

> You said that with both the digital and analog meter connected to the
> CT, you got no readings.  If you connected all three devices in series
> (which is the correct way), no current would flow until you had overcome
> the forward voltage of the bridge in the analog meter.
    This would depend on where any shunt is located.
 
> If you are seeing a scale reading of 18 - 23 amps with the analog meter
> alone connected directly in your circuit without the CT in place, then
> it would indicate that you are actually running 1.8 - 2.3 amps in your
> NST  primary, since 5 amps would drive the analog meter to full scale,
> or the 50 amp position.
> 
> If you connect the current transformer to a good quality DMM set on the
> 10 amp scale, is should be linear down to very small currents.
best
 dwp