Hi, thankyou , but I think ive solved it , ...I was using a digital volt
meter, I disconected the probe wires, and still got a reading , I guess
its picking up inductance or somethin,....I tried an ol analoge meter ,
and got no voltage, so I guess things are ok, but I may add a secound
ground rod just in case, .......THANKS FOR DA HELP !!!!!!!!!!!!! ,dave
>Original poster: Sue Gaeta <sgsparky@xxxxxxxxxxx>
>
>Hi,
>How long is the run between the transformer case and the actual ground
>point? How thick is the conductor? It might be a good idea to run a
second
>ground conductor to a breaker box where all the other grounds are
>terminated in addition to the earth ground connection. Use large
diameter
>wire, 8 AWG or better and keep the run as short as possible.
>
>Most importantly, make sure that the termination connection at both ends
>are clean and solid. Since you got an old transformer there may be some
>corrosion there.
>
>A bad return path is a very dangerous thing, be careful!
>
>